EPS Insulation Thickness and R-Value in Panel Applications
3E-Plus should be used for pipe insulation applications
Expanded Polystyrene Thickness Table and R-Values |
| |
Nominal Density
|
Tested Temp.
|
1.0”
|
2.0”
|
3.0”
|
4.0”
|
5.0”
|
|
R
|
R
|
R
|
R
|
R
|
|
Type 1
|
1.0#
|
@25F
|
4.35
|
8.53
|
13.01
|
17.35
|
21.72
|
|
@40F
|
4.17
|
8.03
|
12.50
|
16.60
|
20.80
|
|
@75F
|
3.85
|
7.69
|
11.49
|
15.38
|
19.23
|
|
Type VIII
|
1.25#
|
@25F
|
4.54
|
9.04
|
13.65
|
18.09
|
22.70
|
|
@40F
|
4.26
|
8.47
|
12.82
|
16.95
|
21.28
|
|
@75F
|
3.92
|
7.81
|
11.76
|
15.63
|
19.61
|
|
Type II
|
1.5#
|
@25F
|
4.73
|
9.45
|
14.21
|
18.90
|
23.62
|
|
@40F
|
4.55
|
9.09
|
13.70
|
18.18
|
22.73
|
|
@75F
|
4.17
|
8.33
|
12.50
|
16.67
|
20.83
|
|
Type IX
|
2.0#
|
@25F
|
5.00
|
10.00
|
17.97
|
23.79
|
30.01
|
|
@40F
|
4.76
|
9.52
|
14.29
|
18.87
|
23.81
|
|
@75F
|
4.35
|
8.70
|
12.99
|
17.24
|
21.74
|
|
| * Conditioned thermal values were determined by ASTM Test Method C 518. |
EPS Typical Thicknesses in Cold Storage Applications
|
Operating Temp Fº
|
Insulation Thickness
|
U Factor
|
|
Btu (Hr) (Sq Ft) (Fº)
|
|
50
|
2” 3”
|
.11 .075
|
|
30
|
3” 4”
|
.075 .060
|
|
15
|
4” 5”
|
.050 .043
|
|
0
|
5” 6”
|
.043 - .037
|
|
-15
|
6” 7”
|
.037 - .032
|
|
-24
|
7” 8”
|
.031 - .027
|
|