ISO-C1 Polyisocyanurate Insulated Panels

Typical Thickness of Insulation Panels: Cold Storage Insulation and Warehouse Insulation

Return to ISO-C1 Polyisocyanurate Insulation Product Description

Cold Storage Insulation Thickness

TYPE OF SPACE

OPERATING TEMP. °F

TYPICAL THICKNESS (inches)

Coolers 54 to 48 1.2
47 to 41 1.7
40 to 34 1.7
33 to 27 2.2
Freezers (Holding) 26 to 20 2.7
19 to 13 2.7
12 to 6 3.2
5 to -1 3.7
-2 to -13 3.7
Sharp Freezers -14 to -25 4.1
-26 to -37 5.1
-38 to -49 6.1
-50 to -61 7.1